When a furnace won’t ignite, the control board has stopped the start-up sequence at one of five checkpoints: no sound, a fan but no glow, a glow but no flame, a flame that dies in seconds, or a furnace that has given up trying. Which one tells most of the story. This guide walks the sequence and names the safe checks.
What happens before the burners light?
A modern gas furnace does not simply light when the thermostat calls. It runs a timed sequence in which each step must prove itself before the next is allowed, and every one of those proofs is a place the sequence can stop. The timings below are from Rheem’s service manual for its 90-plus efficiency furnaces, and other brands run the same steps with slightly different clocks (Rheem M2 series service manual).
| Step | What should happen | What you notice if it stops here |
|---|---|---|
| 1. Call for heat | Thermostat closes the circuit, control board wakes | Nothing at all: thermostat, power, door switch or board |
| 2. Pre-purge | The draft inducer runs for 30 seconds to clear the vent | Small fan hums, then silence: the pressure switch never closed |
| 3. Pressure switch | The switch proves the inducer is moving air and closes | Fan runs and runs: blocked vent, failed switch or kinked hose |
| 4. Igniter warm-up | The igniter heats for 30 seconds until it glows | Fan runs, no orange glow: igniter failed |
| 5. Gas valve opens | Gas flows across the glowing igniter | Glow but no whoosh: gas supply or valve |
| 6. Flame proven | The flame sensor must prove flame within six seconds of the valve opening | Lights, then dies in seconds: flame sensor or gas pressure |
| 7. Blower starts | The main blower starts 30 seconds after the gas valve opens | Flame but no warm air yet: normal for half a minute |
Two details from the same manual matter later on this page. The sequence will not proceed if the pressure switch is already closed before the inducer starts, because that reads as a stuck switch. And the furnace control must prove flame via the flame sensor six seconds after the gas valve opens, which is why a furnace that lights and dies almost immediately is a sensing problem rather than an ignition problem.
Why does it click but never light?
The click depends on the ignition type. Carrier’s explanation is that on a spark-ignition system “you hear repeated clicking from a system using spark ignition as it attempts to ignite the fuel,” while on a hot surface igniter the tell is the opposite: “you don’t see the characteristic orange glow during the ignition sequence” (Carrier, furnace ignitor). A hot surface igniter is a brittle ceramic element that an electrical current heats until it glows and can ignite the gas. They crack, they weaken with age, and they fail most often on the first cold morning of the season because that is the first time the sequence runs after months idle.
If the igniter glows and there is still no flame, the gas is not arriving. The appliance shutoff valve on the gas line beside the furnace has a handle that is parallel to the pipe when open and across it when closed, and that is a thing you can look at without touching anything. Rheem’s manual also notes that air in the gas line can prevent initial ignition after the supply has been off, which is why a furnace sometimes needs a second attempt after gas work. Older furnaces with a standing pilot use a thermocouple instead of a flame sensor, and a pilot that will not stay lit is usually that part.
Why does it light and then go out?
The flame sensor. It is a metal rod in the burner flame that confirms combustion through a process Carrier calls flame rectification, a small current carried through the flame itself. When the rod is coated with oxide, the current drops below the board’s threshold, the board concludes there is no flame, and it closes the gas valve within seconds of opening it. Carrier lists a dirty or faulty sensor as a common reason “a furnace starts but then shuts off after a few seconds,” and its guidance is that the sensor is removed, lightly cleaned and wiped, and replaced if performance does not improve, by a qualified technician (Carrier, furnace flame sensor). Rheem’s service checklist asks the same question, “Is the flame sensor coated?”, and answers it with emery cloth.
Carrier’s warning deserves repeating in full: do not bypass, disconnect or defeat the flame sensor. It is the part that stops gas flowing into a furnace with no flame. A furnace that lights and dies three or four times in a row is behaving exactly as designed, and the fix is a clean or new sensor, not a workaround. HomeGuide puts a flame sensor replacement at $80 to $250 installed and an ignitor at $100 to $250 (HomeGuide), both near the bottom of the repair table.
What is furnace lockout?
A furnace that fails to prove flame does not try forever. The control board allows a set number of attempts, then locks out and shows a fault code on its LED. Rheem’s manual states that on the fifth try for ignition the furnace control is locked out and the red LED blinks four times repeatedly; other brands lock out after fewer attempts, and the count is specific to the control board. The reset Rheem gives is the one most boards share: turn the thermostat to its lowest setting, wait one minute, then turn it to a point above room temperature and the igniter will try again (Rheem M2 service manual).
A furnace won’t ignite again after lockout until the board is reset, and resetting it once is reasonable. Resetting it repeatedly is not, because each attempt that fails has released a little unburned gas into the heat exchanger before the valve closed, and a furnace that locks out again has told you the fault is still there. One reset, then the diagnosis.
Which checks are safe to do yourself?
- Thermostat. Mode on heat, setpoint well above room temperature, fresh batteries if it takes them. Wait five minutes, since most thermostats hold a short delay.
- Power. The furnace breaker, and the switch that looks like a light switch on or beside the furnace. Rheem’s manual notes that proper line voltage polarity must be maintained for the control to operate, which is why a furnace can refuse to work after electrical work even with power present; that one is a technician’s check.
- The blower door. The lower panel must be seated firmly. Rheem’s manual puts the door switch in the line voltage circuit, so a panel knocked loose by a filter change kills the furnace completely and silently.
- The filter. Hold it to a light. A choked filter, common after a Modesto harvest season, overheats the furnace and trips the limit, which looks like an ignition fault from the hallway.
- The gas valve handle. Look at it. Parallel to the pipe is open. Do not operate it if you smell gas.
- The LED code. Most boards show a blink pattern through a window in the lower panel, with the legend printed inside the door. Note it before any reset, because the reset clears it.
- One lockout reset by the thermostat method above.
That is the list. Nothing on it involves removing a burner compartment cover, touching the igniter, the flame sensor, the pressure switch or the gas valve. Carrier’s position on the igniter is that incorrect installation can lead to immediate failure or safety risks, and that handling gas and high-voltage components “requires safety precautions best handled by a certified HVAC technician.” This guide gives no instructions for replacing any of those parts, on purpose.
Why didn’t a new flame sensor fix it?
Because the symptom was never ignition. A common story in forums is a furnace whose burners light, run for a minute or two, then shut off while the blower keeps pushing cold air, and the homeowner has already replaced the flame sensor. Read the sequence again: that furnace proved flame, ran, and was then shut down by a different safety. A high-limit switch that opens because the heat exchanger got too hot is the usual cause, and it opens because airflow is poor: a choked filter, a failed blower, closed registers, or ducts that cannot move the air. The blower continuing to run on its own is the giveaway, because the limit circuit keeps the fan going to cool the exchanger while it holds the gas off.
A pressure switch that opens mid-cycle because the vent is partly blocked does the same thing on a different timer. Both are safeties doing their job, both are diagnosed with instruments, and neither is fixed by a part swap at the sensor. A furnace that lights and then blows cold has its own diagnostic order in the guide to a furnace blowing cold air, and a furnace that does nothing at all starts with what to check before you call when a furnace won’t turn on.
Furnace won’t ignite on a cold morning?
A furnace won’t ignite on the first real cold morning in Modesto more often than on any other day, and it is not coincidence. The igniter has sat idle through a long, dusty summer and the first full sequence of the season is its first stress. The flame sensor has spent the same months oxidizing. The vent has had a season for a bird or a wasp nest to arrive. And a thermostat with tired batteries gets its first real call for heat. The result is a cluster of failures across the city in the same week, and the longest wait for a technician of the year.
The defense is the pre-winter tune-up, which runs the sequence under observation, cleans the sensor, checks the igniter’s resistance, tests the pressure switch and inspects the vent, in October rather than in the first week of December. See the furnace noises that mean shut it off and the ones that can wait. The wider picture of how heating systems in Modesto homes fail in winter, and in what order to check them, is in the complete guide to winter heating systems in Modesto.
When should you call a professional?
The safety line comes first. If you smell gas, an odor like rotten eggs, leave the house with everyone in it and call 911 from outside, then the gas utility. Do not operate the gas valve, do not press a reset, do not touch a light switch on the way out. A carbon monoxide alarm sounding gets the same response.
Short of that, call when the seven safe checks are done and the furnace still will not ignite, when it locks out a second time, when the igniter does not glow, when it lights and dies in seconds, or when it runs and then shuts down with the blower still going. Every one of those is a diagnosis inside the cabinet, with a meter and a manometer, and in Modesto the technician who arrives should be able to tell you which checkpoint failed and show you the reading. A furnace repair visit for an ignition fault is usually a short one when the sequence is read correctly, and a long one when parts are swapped at random.
Frequently asked questions
Why does my furnace click but not ignite?
On a spark-ignition furnace the clicking is the igniter trying and failing to light gas that is not arriving or not igniting. On a hot surface igniter the equivalent symptom is no orange glow. Check the gas valve handle position and the thermostat, then stop; the igniter, the gas valve and the pressure switch are technician parts.
What is a hot surface igniter?
A ceramic element that an electric current heats until it glows hot enough to light the gas, replacing the standing pilot of older furnaces. On Rheem’s sequence it warms for 30 seconds before the gas valve opens. They are brittle, wear with age, and fail most often on the first cold morning.
What is furnace lockout and how do I reset it?
After a set number of failed ignition attempts, five on Rheem’s control, the board stops trying and flashes a code. Rheem’s reset is to turn the thermostat to its lowest setting, wait one minute, then raise it above room temperature. Reset once. A second lockout means the fault is still there.
Why did a new flame sensor not fix it?
Because a furnace that lights, runs a minute and shuts off with the blower still running has proved flame and been stopped by a different safety, usually the high-limit switch over poor airflow or the pressure switch over a vent problem. The sensor was never the fault.
What if the furnace won’t ignite only on cold mornings?
Because the first cold morning is the first full start-up after months idle: an aging igniter takes its first stress, an oxidized flame sensor gets its first test, and a vent blocked over the summer is discovered. A pre-winter tune-up runs that sequence under observation before the weather does.
The short version
Listen and look, in sequence: nothing, fan only, glow, flame, flame that dies. Do the seven safe checks, note the LED code, reset a lockout once. Never bypass the flame sensor and never open the burner compartment. If you smell gas, leave and call 911 from outside. Everything past that line is a technician reading the same sequence with instruments.